Customer wants a home office wall that actually blocks noise from the kids' playroom.

Prompt as given to every model

Customer wants a home office wall that actually blocks noise from the kids' playroom. Wall is already framed as a standard 2x4 single-stud wall. What gives the biggest STC jump for the money, and what kills it?

Model answers

Pick up to two to compare side by side. Score chips fill in as the judge grades.

Laguna S 2.1Score —

Best bang for the buck: Add resilient channel + double-layer drywall (5/8" Type X) on the office side. This typically jumps STC from ~33 (standard) to ~45-48.

  • Resilient channel decouples drywall, breaking sound paths.
  • Double-layer drywall adds mass (mass law: +5 STC per doubling).
  • Type X adds density.

What kills it:

  1. Flanking paths – Sound bypasses walls through ceilings, floors, shared studs. Seal gaps with acoustical caulk.
  2. Single stud wall – Limited decoupling. For major gains, rebuild as staggered or double-stud wall (STC 50+).
  3. Recessed lights or outlets – Penetrate the air gap. Use IC-rated, airtight fixtures and sound gaskets on outlets.
  4. Not addressing the source – Carpet/playroom side needs treatment too. Add mass-loaded vinyl (MLV) or acoustic panels there.

Quick upgrade path:

  • Remove existing drywall on office side.
  • Install resilient channel (RC-1 or RC-2) at 24" o.c.
  • Hang two layers of 5/8" Type X drywall with staggered seams.
  • Seal all joints with acoustical caulk.

Code note: Check local building codes—some jurisdictions require fire-rated assemblies when adding layers. Resilient channel must be installed per manufacturer specs to maintain fire rating.

For maximum performance, consider adding insulation (R-13 mineral wool) in the cavity if not already present.

473 tokens · 9.4s

Judge rubric · pending

Not graded yet. Grading starts when the exam run completes.

Nemotron 3 Ultra 550BScore —

Biggest STC jump per dollar: Decoupling + Mass + Damping (in that order).

  1. Decouple (STC +10–15): Remove existing drywall on one side only. Install resilient channel (RC-1) or, better, hat channel + sound isolation clips (e.g., Kinetics, GenieClip) perpendicular to studs. Clips outperform channel; channel is cheaper but fails if screws hit studs. Code: IRC R702.3.3 (fastening schedule).
  2. Add Mass (STC +5–8): Hang 2 layers of 5/8" Type X drywall on the new channel/clips. Stagger seams. Use Green Glue (or generic viscoelastic damping compound) between the two layers. This adds mass and constrained-layer damping.
  3. Seal Everything (STC +3–5, but kills flanking): Acoustic caulk (not silicone) at perimeter, outlets, penetrations. Putty pads on back of outlet boxes. This is where cheap jobs fail. A 1% gap kills 10+ STC points.

Total assembly (one side treated): ~STC 55–60. Cost: ~$3.50–$5.50/sq ft (clips + 2x 5/8" + GG + caulk).

What kills it:

  • Screws hitting studs through resilient channel (shorts the decoupling).
  • Recessed lights/outlets back-to-back without putty pads or offset boxes.
  • HVAC ducts sharing the cavity (use lined flex duct + soffit).
  • Door: Hollow core = STC 20. Must use solid core + automatic door bottom + perimeter seals. Wall STC means nothing if door is weak.

Don't bother: Fiberglass batts alone (STC +3–4), MLV alone (expensive, hard to seal), double stud wall (too late, framed).

Pro tip: If ceiling is open, treat it same way. Flanking over the top wall plate is the #1 complaint.