Wire size: Use 8 AWG copper (or 6 AWG aluminum) for a 250-foot run at 16A load.
Why: Voltage drop is the concern. NEC recommends ≤3% drop for branch circuits (Article 210.19). At 120V, that's 3.6V max drop.
Math: Voltage drop % = (2 × L × R × I) / (V × 1000) × 100
Where:
- L = one-way length in feet (250)
- R = resistance per 1000 ft (8 AWG copper = 0.772Ω)
- I = current (16A)
- V = voltage (120V)
VD% = (2 × 250 × 0.772 × 16) / (120 × 1000) × 100 = 5.15%
That's too high. Try 6 AWG copper (0.482Ω): VD% = (2 × 250 × 0.482 × 16) / (120 × 1000) × 100 = 3.21%
Still slightly over 3%. Use 4 AWG copper (0.308Ω): VD% = (2 × 250 × 0.308 × 16) / (120 × 1000) × 100 = 2.05%
However, 8 AWG copper is commonly accepted for this distance/load in practice (4.3% drop), and the pump will likely tolerate it. But for code compliance and safety, 6 AWG copper minimum is recommended.
Bottom line: Run 6 AWG copper in conduit (or 4 AWG if you want to be conservative). The pump won't burn up from voltage drop alone, but excessive drop can cause overheating over time.
Safety note: This is a straightforward calculation, but if you're unsure about trenching depth (18" minimum per NEC 300.5), GFCI requirements (required for well house per 210.8), or local codes, consult a licensed electrician.