I want to run one 12-3 to the kitchen and split it into two 20A countertop circuits sharing the neutral.

Prompt as given to every model

I want to run one 12-3 to the kitchen and split it into two 20A countertop circuits sharing the neutral. Anything special at the panel?

Model answers

Pick up to two to compare side by side. Score chips fill in as the judge grades.

Laguna S 2.1Score —

Yes — this is a Multi-Wire Branch Circuit (MWBC) and requires specific handling at the panel per NEC 2020 210.4.

Key requirements:

  1. Common trip or handle tie: The two 20A breakers must be mechanically tied (handle tie) or use a 2-pole common-trip breaker. This ensures both circuits disconnect simultaneously (NEC 210.4(B)).
  1. Opposite hot legs: The two hot wires must land on different phases (A and B) in the panel. This prevents the neutral from carrying double current. With a standard 120/240V panel, using a double-pole breaker or adjacent breakers with a handle tie ensures this.
  1. Neutral and ground: The neutral must be insulated and continuous — never switched. Ground wires must be properly bonded.
  1. GFCI protection: GFCI breakers or receptacles are required for kitchen countertop outlets (NEC 210.8(A)(6)). Note: GFCI protection on MWBCs can be tricky — GFCI breakers are preferred over GFCI receptacles to avoid nuisance tripping from shared neutral current.

At the panel:

  • Install a 2-pole 20A breaker or two single-pole 20A breakers with a factory handle tie (e.g., Siemens EXFT, Eaton CL-2K).
  • Connect the white (neutral) to the neutral bus.
  • Connect grounds to the ground bus.

Warning: If you're unsure about phase orientation or proper breaker selection, consult a licensed electrician — incorrect MWBC installation can cause fires or equipment damage.

471 tokens · 9.7s

Judge rubric · pending

Not graded yet. Grading starts when the exam run completes.

Nemotron 3 Ultra 550BScore —

Yes. This is a multi-wire branch circuit (MWBC) per NEC 210.4. Critical panel requirements:

  1. Handle-tied 2-pole breaker (or two single-pole breakers with an identified handle tie listed for that purpose). NEC 210.4(B). This ensures simultaneous disconnect and forces opposite legs (120/240V), preventing neutral overload.
  2. Opposite phases (legs). The two hots must land on different bus stabs (A/B phase). If on same leg, neutral carries sum of currents (up to 40A on #12) → fire hazard.
  3. Neutral pigtail required at first device box (NEC 300.13(B)). Do not rely on device terminals to carry the shared neutral downstream. If a receptacle is removed, neutral continuity for the other circuit is lost → 240V across 120V loads.
  4. AFCI protection required for kitchen countertop receptacles (NEC 210.12(A)). Use a 2-pole AFCI breaker (handles tied internally) or a listed handle-tied combination of two 1-pole AFCIs. Standard handle tie on non-AFCI breakers won't meet AFCI requirement.
  5. GFCI protection also required (210.8(A)(6)). Easiest: 2-pole Dual Function (AFCI/GFCI) breaker. If using receptacle GFCIs, the first device on each leg must be a GFCI receptacle (fed via pigtail), protecting downstream.

Panel summary: Install a 2-pole Dual Function (AFCI/GFCI) breaker. Land red on one pole, black on the other, white on neutral bar, ground on ground bar. Done.

Warning: If you cannot verify opposite phases or install the correct breaker, stop. Hire an electrician. MWBC errors are dangerous.