Yes — this is a Multi-Wire Branch Circuit (MWBC) and requires specific handling at the panel per NEC 2020 210.4.
Key requirements:
- Common trip or handle tie: The two 20A breakers must be mechanically tied (handle tie) or use a 2-pole common-trip breaker. This ensures both circuits disconnect simultaneously (NEC 210.4(B)).
- Opposite hot legs: The two hot wires must land on different phases (A and B) in the panel. This prevents the neutral from carrying double current. With a standard 120/240V panel, using a double-pole breaker or adjacent breakers with a handle tie ensures this.
- Neutral and ground: The neutral must be insulated and continuous — never switched. Ground wires must be properly bonded.
- GFCI protection: GFCI breakers or receptacles are required for kitchen countertop outlets (NEC 210.8(A)(6)). Note: GFCI protection on MWBCs can be tricky — GFCI breakers are preferred over GFCI receptacles to avoid nuisance tripping from shared neutral current.
At the panel:
- Install a 2-pole 20A breaker or two single-pole 20A breakers with a factory handle tie (e.g., Siemens EXFT, Eaton CL-2K).
- Connect the white (neutral) to the neutral bus.
- Connect grounds to the ground bus.
Warning: If you're unsure about phase orientation or proper breaker selection, consult a licensed electrician — incorrect MWBC installation can cause fires or equipment damage.