This installation has several code violations:
1. NM-B cable in wet locations (NEC 334.12(B)(2)) - NM-B is prohibited in underground conduits and outdoor wet locations. The cable must be replaced with individual THWN conductors or UF cable rated for wet locations.
2. Underground conductor requirements (NEC 300.5) - Direct burial cables need 6" minimum burial depth; PVC conduit requires 18" depth. The installation likely doesn't meet these depth requirements.
3. GFCI protection (NEC 680.22, 680.43) - Hot tubs require GFCI protection, but the 50A GFCI breaker may not be properly coordinated with the spa pack's requirements.
4. Disconnect requirements (NEC 680.12, 680.43) - The non-fused disconnect must be within sight of the tub (max 50 feet) and have a locking mechanism. It also needs to be rated for the application.
5. Conduit fill and wiring method (NEC 300.3, Chapter 9) - Multiple cables in conduit create heat dissipation issues and may exceed fill capacity.
Safety concerns: This setup poses electrocution and fire risks. The NM-B cable will degrade in the wet conduit environment.
Recommendation: This requires immediate correction by a licensed electrician. Replace NM-B with proper wet-rated conductors, ensure proper burial depths, verify disconnect specifications, and confirm GFCI coordination. Do not energize until corrected.