During the last hurricane my neighbor ran his 7500W portable generator into the house by plugging a cord with two male ends into his dryer receptacle and flipping the main breaker off.

Prompt as given to every model

During the last hurricane my neighbor ran his 7500W portable generator into the house by plugging a cord with two male ends into his dryer receptacle and flipping the main breaker off. He says it works great and wants me to make him a heavier cord. What's the problem?

Model answers

Pick up to two to compare side by side. Score chips fill in as the judge grades.

Laguna S 2.1Score —

This setup is extremely dangerous and violates electrical codes. Here's why:

Major Problems:

  1. Backfeeding - Plugging a generator into a dryer receptacle (typically 240V) backfeeds power through your home's wiring, energizing ALL circuits including outlets and appliances that may still be plugged in.
  1. No GFCI Protection - Dryer circuits lack GFCI protection, creating electrocution hazards.
  1. Fire Risk - Using an improvised cord with two male ends can cause arcing, overheating, and fire.
  1. Code Violation - This violates NEC 702.3 and 702.11, which require proper transfer switches and listed generators.

Legal Issues:

  • Creates liability for anyone helping
  • Violates local electrical codes
  • Insurance may not cover damages

Proper Solution: Install a manual transfer switch (NEC 702.11) with dedicated generator inlet wiring. This safely isolates generator power from utility power and protects utility workers from backfed lines.

What You Should Do: Refuse to make this cord. It's illegal and dangerous. Recommend your neighbor hire a licensed electrician to install a proper transfer switch system.

The risk of electrocution, fire, or killing utility workers makes this unacceptable. No "heavier cord" will fix these fundamental safety issues.

412 tokens · 17.7s

Judge rubric · pending

Not graded yet. Grading starts when the exam run completes.

Nemotron 3 Ultra 550BScore —

Stop. Do not make this cord. This is a suicide cord (double male plug) and backfeeding—both are lethal and illegal.

Code Violations (NEC 2023):

  • 404.11 / 702.11: Requires a listed transfer switch or interlock kit to prevent utility/generator parallel operation. Flipping the main breaker is not a code-compliant interlock.
  • 406.5(G): Receptacles must not be energized from the load side. A male plug on a cord energizes exposed blades—shock/electrocution hazard to anyone touching them.
  • 225.30 / 700.5: A portable generator is a separately derived system requiring proper grounding/bonding and transfer equipment.
  • 110.3(B): Equipment must be used per listing. Dryer receptacles (NEMA 10-30/14-30) and breakers are not listed for backfeed.

Specific Hazards:

  1. Lineman Death: If the main breaker fails, is missed, or is turned on by someone else, 7500W feeds the grid at 7.2kV via the pole transformer—killing utility workers.
  2. House Fire: Dryer receptacle (30A) and wiring protected by a 30A breaker. Generator 7500W @ 240V = 31.25A continuous. Overloads the 30A breaker/wiring without tripping instantly (NEC 210.19, 240.4).
  3. Electrocution: Exposed male prongs on generator end and dryer end (if unplugged under load).
  4. No GFCI: Dryer circuits lack GFCI protection required for generator portable outlets (210.8, 590.6).

Correct Solution: Install a UL 1008 listed transfer switch (manual or automatic) or a UL 489 listed circuit breaker interlock kit specific to his panel brand/model with a dedicated generator inlet (NEMA L14-30 or CS6375) and 4-wire cord (L14-30 to CS6365). Requires permit and inspection.

Tell him: "I cannot build this. It violates NEC 406.5(G), 702.11, and endangers lives. Hire a licensed electrician to install a legal transfer switch/interlock and inlet."