Yes—speak up now. Non-IC (non-insulation-contact) recessed cans must not be buried in insulation. With R-38 cellulose blown directly over them, you risk:
- Overheating → fire hazard
- Voided warranty and code violations (NEC 410.16, IMC 605.3)
What to do:
- Tell the GC: Non-IC cans require a 6-inch clearance from insulation on all sides and above.
- Insist on IC-rated cans or install insulation covers/baffles (e.g., Tenmat or similar) rated for direct contact.
- Verify the cans are new-construction or remodel-rated for your ceiling type.
Code check:
- NEC 410.16(C) requires IC-rated fixtures where insulation is installed.
- Local inspectors will flag non-IC cans covered in insulation.
Cellulose is dense and conducts heat poorly—trapped heat from non-IC cans can ignite surrounding material.
Bottom line: Don’t let the insulator blow around non-IC cans without proper protection. Either swap to IC-rated or install certified covers. It’s a small cost now to avoid a dangerous, code-violating mess later.