No, he should not be happy with this "fix." This is a dangerous code violation.
The Problem: NEC 240.4(D)(4) requires 14 AWG copper wire to be protected by a maximum 15 amp overcurrent device. By installing a 20A breaker on 14-2 wiring, the brother-in-law created a fire hazard. The wire can overheat and potentially ignite before the breaker trips.
Why It "Works": The microwave and toaster together likely draw 12-16 amps, which is within the 20A breaker's capacity but exceeds the 15A breaker's rating. However, the 14 AWG wire may not safely handle sustained loads above 15 amps.
Proper Solutions:
- Revert to 15A breaker and use appliances one at a time
- Upgrade to 12-2 wiring and install a 20A breaker (NEC 210.19(A)(1))
- Install a dedicated 20A circuit for the microwave (NEC 210.11(C)(1) requires kitchen small appliance branch circuits)
Immediate Action Required: Replace the 20A breaker with a 15A breaker immediately. This is not a permanent solution but prevents potential wire overheating.
Bottom Line: This setup violates electrical code and poses a serious fire risk. A licensed electrician should properly upgrade the circuit wiring to handle the load safely.