Service call: a #12 neutral in a 10-year-old panel is scorched and the wire nut in the kitchen ceiling box is melted, but neither breaker on that 12-3 ever tripped.

Prompt as given to every model

Service call: a #12 neutral in a 10-year-old panel is scorched and the wire nut in the kitchen ceiling box is melted, but neither breaker on that 12-3 ever tripped. The two hots are on a pair of single-pole 20s stacked in slots 3 and 5 on the same side of the panel. Both circuits measure normal voltage. What happened?

Model answers

Pick up to two to compare side by side. Score chips fill in as the judge grades.

Laguna S 2.1Score —

What happened: an open neutral on a multi-wire branch circuit (MWBC).

Here's the sequence:

  1. Improper MWBC setup: The two 20A single-pole breakers in slots 3 and 5 are on the same leg (both A or both B phase). A proper MWBC requires the two hots to be on opposite legs (one on A, one on B) so the neutral carries only the difference in current between the two circuits.
  1. Neutral overload: Because both breakers are on the same leg, the neutral carries the sum of both circuit currents instead of the difference. If both circuits were drawing near 20A simultaneously, the neutral would be carrying 40A on a #12 conductor—well beyond its 20A rating.
  1. Overheated neutral: The #12 neutral couldn't handle the overload, causing it to overheat. This led to the scorched wire at the panel and the melted wire nut in the kitchen ceiling box.
  1. Why breakers didn't trip: Standard single-pole breakers only monitor current on their own hot leg. Since the neutral current wasn't flowing through either breaker, neither saw an overcurrent condition. The breakers only protect against hot-to-neutral or hot-to-ground faults on their individual circuits.

Fix: Install a common-trip double-pole breaker (or use a handle tie on adjacent breakers on opposite legs) to properly create the MWBC. This ensures the neutral only carries unbalanced current and provides proper overcurrent protection for the shared neutral.

Safety note: This is a fire hazard. Turn off both breakers and correct the setup before restoring power.

499 tokens · 8.0s

Judge rubric · pending

Not graded yet. Grading starts when the exam run completes.

Nemotron 3 Ultra 550BScore —

This is a classic lost neutral on a multi-wire branch circuit (MWBC). The two single-pole breakers in slots 3 and 5 are on the same leg (phase) of the panel.

What happened: Because both hots are on the same phase, their currents add on the shared neutral instead of canceling. If Circuit A draws 15A and Circuit B draws 10A, the neutral carries 25A through a #12 wire rated for 20A. The neutral overheats at the panel lug and the ceiling box splice (the highest resistance points) without ever tripping the 20A breakers, which only monitor their individual hot legs.

Code Violations (NEC):

  • 210.4(B): MWBCs require a common maintenance disconnect (2-pole breaker or listed handle tie) to ensure both legs open simultaneously.
  • 210.4(A): MWBC hots must originate from opposite phases (A/B) so neutral current equals the difference of the loads.
  • 300.13(B): Neutral continuity must not depend on device connections (pigtailing required at devices, which you likely have, but the wire nut failed due to heat).

Required Fix:

  1. Kill power. Verify both legs are dead.
  2. Replace the two single-pole breakers with a listed 2-pole 20A breaker (or install a UL-listed handle tie only if the breaker manufacturer permits it for that model).
  3. Relocate one breaker so the pair occupies adjacent vertical slots (e.g., 3 & 4 or 5 & 6). This guarantees opposite phases (A-B) in standard panels.
  4. Cut back scorched neutral insulation; re-terminate in panel with antioxidant paste.
  5. Replace the melted ceiling box wire nut with a high-temp rated connector (e.g., ceramic or high-temp push-in) and verify the box volume (314.16) isn't exceeded.

Do not re-energize until the 2-pole breaker is installed on opposite phases. This is a fire hazard.