What's the accepted evacuation target and decay test before I release charge on a new residential split system, and where should the micron gauge be?

Prompt as given to every model

What's the accepted evacuation target and decay test before I release charge on a new residential split system, and where should the micron gauge be?

Model answers

Pick up to two to compare side by side. Score chips fill in as the judge grades.

Laguna S 2.1Score —

Evacuation Target:

  • Pull vacuum to 500 microns or below (field standard).
  • Hold for 15–30 minutes; maximum rise should be ≤100 microns (i.e., final reading ≤600 microns).
  • If it climbs past 700–1,000 microns, suspect a leak or outgassing.

Decay (Hold) Test:

  • Isolate the system with core tools or valve closures.
  • Monitor for 15 minutes minimum (longer in humid conditions).
  • Acceptable decay: ≤100-micron rise.

Micron Gauge Placement:

  • Install the micron gauge at the service port on the low side (suction line).
  • Remove the gauge hose from the vacuum pump side and connect directly to the low-side service port via a dedicated vacuum-rated hose.
  • Do not leave the gauge connected to the vacuum pump during the decay test — isolate it.

Code Reference:

  • ACCA AHR2-2018 and ASHRAE Standard 15 recommend deep vacuum to ≤500 microns for hermetic systems.
  • Section 608 requires evacuation to remove noncondensables and moisture.

Pro Tip:

  • Use a vacuum tree with a dedicated gauge port and core depressor for accuracy.
  • Always replace filter-driers if the system was open to atmosphere.

If readings don’t hold, recheck for leaks, especially at flares and joints.

425 tokens · 9.3s

Judge rubric · pending

Not graded yet. Grading starts when the exam run completes.

Nemotron 3 Ultra 550BScore —

Evacuation Target: 500 microns (or less) is the industry standard per ASHRAE Guideline 3-2016 and manufacturer specs. Many OEMs now require 250–300 microns for POE oils (R-410A, R-32, R-454B). Check the install manual.

Decay Test (Standing Vacuum Test):

  1. Pull system to target (e.g., 250 microns).
  2. Isolate pump: Close core tool valves at the system ports. Turn pump off.
  3. Wait 10–15 minutes minimum (30 min preferred).
  4. Pass Criteria: Micron reading does not rise above 500–1000 microns (varies by OEM; 500 is safe baseline). If it rises steadily → leak. If it plateaus → moisture/outgassing; evacuate longer.

Micron Gauge Placement: At the system service ports (core tools), NOT at the pump.

  • Use valve core removal tools (core tools) on both liquid and suction ports.
  • Connect micron gauge to the side port of one core tool (usually suction side for larger volume).
  • Connect vacuum pump to the other core tool.
  • Why: Measures actual system vacuum. Pump inlet reads lower (pump vacuum), misleading you. Hose/core depressor restriction creates pressure drop; gauge at pump won't see system pressure.

Critical Steps:

  • Remove Schrader cores (use core tools).
  • Use 3/8" or 1/2" vacuum hoses (short, large ID).
  • Nitrogen sweep (1–3 PSI) before evacuation if system was open >1 hr.
  • Triple evacuation (nitrogen break) only if required by manual or extreme moisture suspected.

Release Charge: Only after passing decay test. Open liquid line service valve first (slowly), then suction.