Manual D Duct Sizing Steps:
- Start with the furnace/air handler - Note the blower's total CFM (typically 400 CFM per ton, so ~1,200 CFM for 3-ton).
- Lay out the trunk line - This is the main supply duct running from the air handler. Size it based on the total CFM it needs to carry and the available space. For 1,200 CFM, you'll likely use 10" x 16" or 12" x 14" rectangular duct (or 14" round).
- Work downstream to branches - Each branch takes off from the trunk to feed a room or zone. Calculate the CFM needed for each branch based on Manual J room loads.
- Size each branch - Use the Manual D worksheet or ductulator. Input the branch's CFM and the maximum friction rate (typically 0.10 inches water column per 100 feet for supply). The tool gives you the required duct size.
- Check velocity - Ensure velocities stay reasonable (supply: 600-900 FPM, return: 500-700 FPM) to avoid noise.
- Account for fittings - Add equivalent length of elbows, transitions, and fittings to your total duct length when calculating pressure drop.
Key Rule: The trunk must be sized to carry the sum of all downstream branch CFMs. As you add branches, the remaining trunk CFM decreases, so you may need to reduce trunk size partway down.
Pro tip: Use a ductulator or online calculator - Manual D tables are tedious. Always verify your total system pressure drop matches the blower curve.
If you're doing this for a real install, have a pro review your numbers - improper duct sizing kills efficiency.