BlueCollarBench

Trades/HVAC

HVACTask HV-014journeymanKnowledgeUS

I've installed a new 80,000 BTU gas furnace.

Prompt as given to every model

I've installed a new 80,000 BTU gas furnace. How do I check temperature rise and what do I do if it's out of range?

Model answers

Pick up to two to compare side by side. Score chips fill in as the judge grades.

Laguna S 2.1Score —

Checking Temperature Rise:

  1. Turn off power to the furnace.
  2. Remove filter and ensure blower is clean.
  3. Connect a digital multimeter with a temperature probe or use a non-contact thermometer.
  4. Measure supply air temperature at the furnace outlet (plenum) and return air temperature at the filter rack or return duct.
  5. Calculate ΔT: Supply temp minus return temp.
  6. Compare to manufacturer’s data—typically 40–70°F for 80,000 BTU furnaces, but check your specific model’s rating plate or installation manual.

If Out of Range:

  • Too high (overheating):
  • Check airflow—clean/replace filter, verify blower wheel is clean and spinning correctly.
  • Confirm blower motor is wired for correct speed (high heat tap).
  • Check ductwork for restrictions or closed dampers.
  • Verify gas pressure per manufacturer specs (requires manometer).
  • Too low:
  • Check for restricted airflow (dirty filter, closed registers).
  • Verify blower is running at proper speed.
  • Check for duct leakage or disconnected ducts in unconditioned spaces.

Safety Note: Gas pressure adjustments and internal component testing should only be done by a licensed HVAC technician. Improper adjustments can cause carbon monoxide production or equipment damage.

Code Reference: Per IRC G2405.2, furnaces must be installed per manufacturer’s instructions, including proper airflow and temperature rise. NFPA 110 requires safe operating conditions.

If issues persist after basic checks, contact a licensed HVAC contractor.

453 tokens · 6.9s

Judge rubric · pending

Not graded yet. Grading starts when the exam run completes.

Nemotron 3 Ultra 550BScore —

Checking Temperature Rise (ΔT):

  1. Prep: Run furnace 10–15 mins for steady state. Confirm manifold pressure matches nameplate (typically 3.5" WC natural, 10" WC LP).
  2. Measure: Use calibrated digital probes. Return: Probe in return plenum before filter/coil. Supply: Probe in supply plenum after heat exchanger, before A-coil (drill 3/8" hole, seal after).
  3. Calculate: ΔT = Supply Temp – Return Temp.
  4. Compare: Check nameplate for Rated Rise Range (e.g., 30–60°F, 40–70°F). Your measured ΔT must fall within this range.

If Out of Range:

  • ΔT Too HIGH (Low Airflow) — Most Common:
  • Risks: Overheating, cracked heat exchanger, high-limit trips, short cycling.
  • Fixes: 1. Check filter (clean/new, MERV ≤8 unless system rated higher). 2. Verify blower speed tap: Move to higher heating speed tap (check wiring diagram; often "Heat" tap is separate from "Cool"). Do not exceed 0.5" WC TESP (Total External Static Pressure) per nameplate. 3. Check duct sizing/restrictions: Undersized returns, closed dampers, crushed flex, dirty A-coil. 4. Verify gas input: Clock meter (IFGC 402.4) or check manifold pressure. Derate only if overfired (max 10% per NFPA 54/IFGC).
  • ΔT Too LOW (High Airflow/Underfired):
  • Risks: Condensation in primary heat exchanger (non-condensing), poor comfort, potential corrosion.
  • Fixes: 1. Lower blower speed tap (if above min CFM). 2. Verify gas input — increase pressure only to nameplate spec. 3. Check for excessive bypass air / zoning bypass damper open.

Critical: After any adjustment, re-measure ΔT and TESP. Document final values. If ΔT cannot be brought into range with clean filter & correct speed taps, duct system is deficient — requires redesign.

635 tokens · 6.7s

Judge rubric · pending

Not graded yet. Grading starts when the exam run completes.