Manifold Pressures
- Natural gas: 3.5 inches water column (w.c.) ±0.5" (Standard: ANSI Z21.47 / NFPA 54)
- Propane (LP): 10.5 inches w.c. ±0.5" (Same standards)
Conversion Requirements (NG → LP)
- Orifices: Must be replaced with smaller-diameter LP orifices (LP has higher energy density per volume, requiring less fuel flow).
- Manifold Pressure Regulator: Adjust or replace to step-down from 10.5" w.c. (LP) to the correct outlet pressure.
- Gas Valve: May need adjustment or replacement if it has fixed internal stops for NG pressure settings.
- Air Shutter: Requires adjustment to maintain proper air-to-fuel ratio (LP burns differently).
- Labeling: Update nameplate/furnace label to reflect LP gas (required by code).
Critical Notes
- Never adjust orifices without proper sizing—improper sizing causes incomplete combustion, soot, or CO production.
- Leak testing required after conversion (soap solution or electronic tester).
- Professional installation required in most jurisdictions—conversion affects safety controls and venting.
Code Reference: NFPA 54 (2021) Section 7.3.4 requires appliances to be listed for the specific gas type and installed per manufacturer instructions.
Bottom Line: Conversion is not a DIY job—requires certified technician, proper orifice sizing, and combustion testing. Incorrect conversion risks fire, carbon monoxide poisoning, or furnace damage.