Key Readings for 90+ Condensing Furnace Combustion Analysis:
- Oxygen (O₂): Target 2-4% (condensing furnaces operate with excess air).
- Carbon Monoxide (CO): Must be <50 ppm (ideally <10 ppm) in undiluted stack gas.
- Carbon Dioxide (CO₂): Typically 8-10% for natural gas.
- Stack Temperature: Should be <125°F (ideally 90-110°F) for high efficiency.
- Efficiency: Should be ≥90% (as rated).
- Draft/Pressure: Negative draft in combustion chamber; vent should be neutral to slightly negative.
Stop-the-Job Numbers (Unsafe Conditions):
- CO > 50 ppm in stack gas (immediate hazard).
- O₂ > 15% or <1% (indicates combustion air issues).
- Stack temp > 200°F (possible heat exchanger breach or improper venting).
- Visible soot or rollout at heat exchanger (safety hazard).
Code Reference: Per NFPA 54 (2020), Section 7.11, CO in occupied spaces must not exceed 35 ppm (8-hour exposure). For stack CO, ANSI Z21.45 requires <50 ppm for gas appliances.
Action: If any stop-the-job number is hit, shut down the furnace, ventilate, and investigate (e.g., cracked heat exchanger, blocked vent, or improper gas pressure). Retest after corrections.