Based on the 2020 International Residential Code (IRC), your 6×8×9 ft closet provides 432 cubic feet of air. For a gas appliance like your 80% efficient furnace, the IRC requires 50 cubic feet of air per 1,000 BTU/h of input rate.
Your furnace’s input rate is 100,000 BTU/h ÷ 0.80 efficiency = 125,000 BTU/h. Required combustion air: 125,000 ÷ 1,000 × 50 = 6,250 cubic feet.
Your closet only provides 432 cubic feet—far short of the requirement.
What You Need:
- Permanent openings sized to provide the required air: - Total free area needed: 6,250 ÷ 60 minutes = 104 square inches of net free area. - Provide two openings: one within 12 inches of the floor and one within 12 inches of the ceiling. - Each opening must be at least 52 square inches (e.g., a 7"×7.5" vent or equivalent).
- Alternative: If the closet shares air with the home, you may qualify for reduced requirements under IRC Section G2407.5.2, but this typically applies to direct-vent or sealed-combustion units—not standard 80% furnaces.
Bottom Line:
Install two properly sized permanent vents (one high, one low) connecting the closet to adjacent spaces or outdoors. Without adequate combustion air, the furnace risks incomplete combustion, carbon monoxide production, and safety hazards.
If unsure about venting paths or local code amendments, consult a licensed HVAC technician.