Furnace Gas Shutoff Valve Location
The gas shutoff valve must be installed within 6 feet of the furnace and readily accessible without tools (IRC Section G2418.2). It should be on the upstream (supply) side of the furnace, before the gas enters the unit. The valve must be a manual, full-port ball valve or similar approved type.
Drip Leg Requirement
Yes, a drip leg (sediment trap) is required by IRC Section G2419.12. It must be installed on the appliance side of the shutoff valve, before the gas connection to the furnace. The drip leg should:
- Be a minimum 3-inch vertical pipe drop
- Use a tee fitting oriented so the outlet faces downward
- Include a capped nipple to collect debris and condensate
Installation Notes
- Use proper gas-rated piping (black iron, CSST, or approved flexible connectors)
- Ensure all joints are properly sealed with gas-rated thread sealant or tape
- Test for leaks with a soap solution or electronic leak detector after installation
- Some local codes may have additional requirements—check with your AHJ
Safety Warning: Gas work can be dangerous. If you're not experienced with gas piping, hire a licensed HVAC technician or plumber. Improper installation can cause leaks, fire, or carbon monoxide poisoning.