Disconnect Location (NEC 440.14): Must be within sight of the condenser (≤50 ft). If not visible, install a lockout/tagout disconnect at the unit and a remote one at the service panel.
Breaker/Wire Sizing (NEC 440.22, 440.23):
- Nameplate FLA → Multiply by 1.25 for minimum breaker size. - Example: 20A FLA × 1.25 = 25A breaker minimum.
- Wire Ampacity (NEC 440.22): - Size wire to 1.25 × FLA (same as breaker). - Use 75°C column if terminals rated for it (NEC 110.14). - Example: 25A required → #10 AWG copper (30A at 75°C).
- Voltage Drop (optional but recommended): - Keep ≤3% for efficiency.
Key Notes:
- If nameplate specifies max breaker (e.g., 30A), use that instead of 1.25×FLA if higher.
- For heat pumps, account for reversing valve draw.
- Always verify local codes may be stricter.
Safety Warning: If unsure about electrical calculations or local requirements, hire a licensed electrician. Improper sizing can cause fire or equipment damage.