What's wrong:
- Oversized system: 5 tons for 2,000 sq ft in Jacksonville is excessive. ACCA Manual J load calculations typically yield ~1.5–2 tons for this size home in Climate Zone 3.
- Short cycling: 8-minute run times confirm oversizing. The unit cools too fast, never reaching steady-state dehumidification.
- Humidity issues: Single-stage systems need 15–20+ minutes to effectively remove moisture. Short cycles leave the coil too warm to dehumidify properly, causing the "sticky" feeling.
What should have happened:
- Manual J Load Calculation: Required by IECC 2020 (Florida adopted 2020 code). This determines actual cooling load based on insulation, windows, orientation, occupancy—not square footage rules of thumb.
- Proper Equipment Sizing: Likely 2–3 tons max. Oversizing by 2x+ is common but incorrect.
- Two-Stage or Variable-Speed Equipment: Better humidity control and longer run cycles.
- Duct Sealing: Attic ducts in Florida often leak 20–30%. Duct blasting and mastic sealing should accompany any replacement.
Immediate fix:
- Install a properly sized 2-stage heat pump (2.5–3 tons) with variable-speed blower.
- Add a whole-house dehumidifier if humidity remains problematic.
- Seal and insulate ductwork.
Code note: Florida Administrative Code 62-6-20 mandates ACCA Manual J/S/D for new HVAC installations. The salesman's "400 sq ft per ton" rule violates proper protocol.
The homeowner is paying for inefficiency and discomfort. A real load calc and right-sized equipment will solve both.