Three code violations on one circuit:
- Conductor Ampacity (310.16 / 334.80): #8 NM-B (Romex) is limited to the 60°C column (334.80). Ampacity = 40 A. You cannot use the 75°C column (50 A) for NM-B. A 50 A breaker on 40 A wire is a fire hazard.
- Breaker Sizing / MCA (440.4(B), 110.3(B)): Nameplate MCA = 52 A. 440.4(B) requires branch circuit conductors and OCPD ≥ MCA. A 50 A breaker violates the listing.
- MOP Violation (440.22): Nameplate MOP = 60 A. While a 50 A breaker is under the MOP, it fails the MCA requirement above. The correct OCPD is 60 A.
The Fix:
- Wire: Pull #6 NM-B (55 A @ 60°C) or #6 THHN in conduit (65 A @ 75°C).
- Breaker: Install a 60 A 2-pole breaker.
- Lugs: Verify air handler terminals accept #6 CU (most 60 A units do).
Note on "One Circuit": Landing blower + strips on a single circuit is standard for "single circuit entry" kits if the nameplate gives a single MCA/MOP (which yours does). No separate blower circuit needed.
Bottom line: Installer used wire rated 40 A on a 50 A breaker for a load requiring 52 A minimum. Re-pull with #6 CU and a 60 A breaker.