IRC R506 (2021/2024) governs residential slabs-on-grade.
Thickness: 3½ inches minimum (R506.1). Exception: 3 inches allowed for garage floors only if no vehicle loads (rarely practical).
Base Course (Capillary Break): 4 inches minimum of clean, graded crushed stone, gravel, or crushed blast-furnace slag (R506.2.1). Material must pass a 2-inch sieve; ≤5% passing a No. 4 sieve. Compacted.
Vapor Retarder: 6-mil (0.006 in.) polyethylene or equivalent Class A vapor retarder (ASTM E1745) required under slab in heated/cooled spaces (R506.2.3).
- Lap joints 6 inches minimum, taped.
- Seal all penetrations (pipes, columns).
- Place directly under slab (on top of base course)—not under the base. ACI 302.1R recommends this to prevent blotching/curling; IRC allows it above or below base, but above is standard practice.
Reinforcement: Not required by code for non-structural slabs, but #3 rebar at 18" o.c. each way or 6x6-W2.9xW2.9 WWF is standard for crack control. Support on chairs—not pulled up during pour.
Prep: Subgrade uniform, compacted, free of organics/debris (R506.2). Dampen base before pour to prevent rapid moisture loss.
Garage note: Slab must slope ⅛"/ft minimum toward door or drain (R309.1).
Commercial/structural slabs follow ACI 318/360—different rules.