Shingle Rating: You need ASTM D7158 Class H (150 mph) rated laminated shingles. Florida Product Approval or Miami-Dade NOA listing is mandatory. Verify the specific product approval for your exact shingle model.
Nailing (Critical for High Wind):
- Fastener: Ring-shank roofing nails, minimum 12-gauge, 3/8" head diameter. Length must penetrate ¾" into sheathing or through plywood/OSB. Staples are prohibited in HVHZ (High Velocity Hurricane Zone) and strongly discouraged statewide for 140 mph.
- Pattern: 6 nails per shingle (not 4). This is required by FBC R905.2.6.1 for >130 mph zones and most Class H manufacturer instructions.
- Placement: Drive nails 1" above the cutout (or per manufacturer's "high wind" line), 1" from each end, and evenly spaced (approx. 7-7/8" o.c. for standard 39-3/8" shingles). Nails must be flush, not overdriven or angled.
- Decking: Min. 15/32" plywood or 7/16" OSB (FBC R803.2.2). Verify fastener penetration.
Underlayment: FBC R905.1.1 requires two layers of ASTM D226 Type II (No. 30) felt or one layer of approved synthetic (per FL Product Approval) with capped head nails (cap nails) spaced per approval (typically 6" edge / 12" field). Self-adhering membrane (ASTM D1970) at eaves, valleys, ridges, and penetrations.
Code References: FBC 2023 (8th Ed.) R905.2.6.1 (Fasteners), R905.2.4 (Wind Resistance), R905.1.1 (Underlayment), R803.2.2 (Sheathing). Check local amendments.
Bottom Line: Use Class H shingles, 6 ring-shank nails/shingle placed precisely, approved underlayment system. Pull the specific manufacturer's High Wind Application Instructions and the Florida Product Approval sheet for the exact shingle on the job site. Follow the stricter of the two.