Stringer Layout:
- Total rise: 108"
- Number of risers: 108 ÷ 7.5" = 14.4 → 15 risers (standard max riser = 7.5", IRC R314.4)
- Actual rise: 108 ÷ 15 = 7.2" per riser
- Run: Use 1" tread + 2x12 depth (11.25") = 11.25" run (IRC R314.3.1 requires min 10" tread depth)
Layout Steps:
- Mark 15 risers at 7.2" each on 2x12 stringer.
- Mark 15 tread runs at 11.25" each.
- Cut top plumb cut (15 risers × 7.2" = 108" total).
- Bottom: Cut level for first tread installation.
Watch Points:
- Bottom: Ensure first riser aligns with floor framing; may need to adjust for subfloor thickness.
- Throat: Maintain 3.5" minimum clear depth above cut (IRC R314.3.1) – don’t overcut.
- Top: Secure with ledger or framing screws into floor structure.
Code Check:
- Max riser: 7.5" (7.2" OK)
- Min tread: 10" (11.25" OK)
- Handrail required if >2 risers (IRC R314.9).
Use a framing square or stair gauge for precise cuts. Double-check measurements before cutting.