No, this is not good enough and likely violates code.
The Tapcon approach fails on multiple fronts:
Code Compliance:
- IBC 2308.8.2 requires anchor bolts to be installed per ASTM F1554 Grade 36 (wet-set J-bolts) with specific embedment depths and spacing.
- IRC R602.11 requires anchor bolts at corners and every 6 feet maximum spacing, with the first bolt within 12 inches of corner (not 30").
Structural Issues:
- 30-inch corner distance creates excessive lever arm, concentrating uplift forces on the two bolts nearest the corner.
- Tapcons (concrete screws) have significantly lower pullout strength than J-bolts and aren't designed for seismic/wind uplift loads.
- 8-foot spacing exceeds the 6-foot maximum for shear walls.
Required Fix: Install additional wet-set anchor bolts (ASTM F1554 Gr. 36) at:
- Maximum 6 feet on center along the wall
- Within 12 inches of each corner
- At 4 feet on center in corner regions (per engineering judgment)
If the existing J-bolts are too far from corners, you'll need to either:
- Core drill and install new wet-set anchors, or
- Epoxy-set threaded rods (ASTM F1554) as supplementary anchors
Bottom line: Tapcons won't provide adequate uplift resistance. This needs proper anchor bolt placement per code, or you risk structural failure under wind/seismic loads.