Device Required: Reduced Pressure Principle Assembly (RP) — not a PVB, SVB, or DCVA.
Code Basis (IPC/IRC/UPC):
- Irrigation systems are high-hazard (contain fertilizers, pesticides, animal waste) → health-hazard cross-connection.
- IPC §608.16.2 / UPC §603.4.2 / IRC §P2902.5.2: Only RP or air gap allowed for high-hazard connections.
- PVB/SVB permitted only for low-hazard or where no backpressure possible (rare in irrigation).
- DCVA never allowed for health hazards.
Installation Rules:
- RP must be ≥12″ above highest downstream outlet (IPC §608.16.2) — usually means above grade in a heated enclosure or vault with drain.
- Horizontal installation only if listed for it (most aren’t).
- Full-port ball valves on inlet/outlet; test cocks accessible.
Testing:
- Yes — initial test required before use, then annually (IPC §608.17 / UPC §603.4.2).
- Must be tested by certified backflow assembly tester (ASSE 5110 or local equivalent).
- Submit results to water purveyor / AHJ.
Permit/Inspection:
- Almost always requires plumbing permit and rough-in + final inspection.
- Many jurisdictions require letter of compliance from tester before final.
Bottom line: Install an RP, pull a permit, get it tested by a certified pro before turning water on. Anything less fails inspection and risks contamination liability.