Tech is at a 3-ton R-410A TXV system on a 68 F afternoon in October. He hooks up gauges, sees 105 psi suction, says 'that's low for 410,' and starts adding refrigerant until suction reads 118 and the line is sweating. Subcooling is now 22 F. What did he do wrong?

Model A

He overcharged the system by using suction pressure and line sweating as charging indicators on a TXV system. This is a critical error.

What he did wrong:

  1. Ignored the metering device: TXV systems must be charged by subcooling (or weigh-in), not suction pressure or superheat. The TXV maintains constant superheat; adding refrigerant only raises head pressure and subcooling.
  2. Misdiagnosed "low" suction: At 68°F ambient, 105 psi suction (~34°F SST) is normal. Design SST is typically 35–45°F below return air temp (e.g., 75°F RA → 30–40°F SST). He chased a ghost problem.
  3. Created a new problem: 22°F subcooling is excessive (target is typically 10–12°F ±3°F per manufacturer). This indicates liquid backing up in the condenser, raising head pressure, increasing compressor work/amp draw, and reducing capacity/efficiency. It risks compressor damage (liquid floodback if TXV hunts) and wasted energy.

Correct procedure (per ACCA Standard 5 / Manufacturer specs):

  1. Verify airflow (400 CFM/ton), clean coils, correct fan speed.
  2. Let pressures stabilize (10–15 min).
  3. Measure liquid line temp and high-side pressure (convert to saturation temp).
  4. Subcooling = Sat Temp – Liquid Line Temp.
  5. Add/remove refrigerant only to hit manufacturer’s target subcooling.

Result: System is now overcharged. Recover refrigerant until subcooling matches the nameplate spec.